Guarded Analog Output Modules
(T7480)
PD
-
7026
Mar
-
06
17
Figure
10
. Guarded
Analog Output Module Calibration
Potentiometer Locations.
The I/O extender module has jumper posts that allow you to
connect or disconnect the I/O slot field wiring on the I/O
chassis to the printed circuit board plugged into the I/O
extender. During the calibration steps you will remove any
jumpers installed on these posts in order to connect the
precision load resistors to the analog outputs. Figure
11
shows the jumper posts to which you should connect the
precision resisto
rs for each analog output channel.