Rockwell-automation T3441A ICS Regent DC Digital Output Module 24 VDC Bedienungsanleitung

Stöbern Sie online oder laden Sie Bedienungsanleitung nach Ausrüstung Rockwell-automation T3441A ICS Regent DC Digital Output Module 24 VDC herunter. Rockwell Automation T3441A ICS Regent DC Digital Output Module 24 VDC User Manual Benutzerhandbuch

  • Herunterladen
  • Zu meinen Handbüchern hinzufügen
  • Drucken
  • Seite
    / 14
  • Inhaltsverzeichnis
  • LESEZEICHEN
  • Bewertet. / 5. Basierend auf Kundenbewertungen
Seitenansicht 0
ICS Regent
®
PD
-
6015
Industrial Control Services
1
DC Digital Output Module
24 VDC
(T3441A)
Issue 1,
March, 06
The DC digital output module provides cont
rol of 16 user
output loads. One type of module is available to interface to
outputs powered from a nominal 24 VDC field power supply.
Each module's triplicated I/O Safetybus interface ensures that
no Regent system failure can incorrectly apply power to an
output, and that no failure in the module can affect the
operation of the Regent system or other I/O modules in the
system.
Features
·
Sixteen output circuits, configured as two isolated groups of
eight circuits each.
·
Hot
-
replaceable.
·
Automatic self
-
testing of triplicated I/O Safetybus circuits and
many simplex logic circuits.
·
2 amp output circuits.
·
Individual front panel indicators on each module show
active/fault, shutdown, blown fuse, and output on/off status
(field side).
·
2500 volt minimum electrical isolation between field and logic
circuits.
·
TÜV certified, Risk Class 5, non
-
interfering.
Seitenansicht 0
1 2 3 4 5 6 ... 13 14

Inhaltsverzeichnis

Seite 1 - ICS Regent

ICS Regent® PD-6015 Industrial Control Services 1 DC Digital Output Module 24 VDC (T3441A) Issue 1, March, 06 The DC digital output module provides

Seite 2

DC Digital Output Module (T3441A) 10 Industrial Control Services 1) Set the Module Type: Position the cursor on the module slot you wish to defin

Seite 3 - Front Panel Indicators

(T3441A) DC Digital Output Module PD-6015 Mar-06 11 Name Also called the tag name, this is the name used in the application program to reference

Seite 4

DC Digital Output Module (T3441A) 12 Industrial Control Services control logic by using a contact element (or similar element) with the output poi

Seite 5

(T3441A) DC Digital Output Module PD-6015 Mar-06 13 Minimum Load 0 mA On State Drop 0.5 volts maximum @ 2 amps Surge Current 15 amps, 20 msec Out

Seite 6 - Application

DC Digital Output Module (T3441A) 14 Industrial Control Services Safety Certified to DIN V VDE 0801 (non-interfering) and designed to meet UL 508

Seite 7

DC Digital Output Module (T3441A) 2 Industrial Control Services Module Operation A block diagram of a typical 24 VDC digital output module is sho

Seite 8 - Fault Mode Jumper

(T3441A) DC Digital Output Module PD-6015 Mar-06 3 When the output is logically turned on, the field device is energized, and when the output is

Seite 9 - Configuration

DC Digital Output Module (T3441A) 4 Industrial Control Services Active and Fault Status Indicators These green and red LEDs indicate the overall

Seite 10 - Industrial Control Services

(T3441A) DC Digital Output Module PD-6015 Mar-06 5 Figure 2. 24 VDC Digital Output Module.

Seite 11

DC Digital Output Module (T3441A) 6 Industrial Control Services Application Simplex Configuration Digital output modules provide a suitable inter

Seite 12

(T3441A) DC Digital Output Module PD-6015 Mar-06 7 Figure 4. Module Wiring.

Seite 13

DC Digital Output Module (T3441A) 8 Industrial Control Services Fault Mode Jumper The fault mode jumper is located behind the ID switch cover in

Seite 14

(T3441A) DC Digital Output Module PD-6015 Mar-06 9 Figure 5. Installing Slot Keys. Configuration Each output module is configured using the