Rockwell-automation Logix5000 Controllers Messages Programming Manual Bedienungsanleitung Seite 14

  • Herunterladen
  • Zu meinen Handbüchern hinzufügen
  • Drucken
  • Seite
    / 34
  • Inhaltsverzeichnis
  • LESEZEICHEN
  • Bewertet. / 5. Basierend auf Kundenbewertungen
Seitenansicht 13
Chapter 1 Controller messages
To determine or change the number of unconnected buffers, use a MSG
instruction.
The range is 10 to 40 unconnected buffers.
The default number is 10.
Each unconnected buffers uses 1.1 KB of memory.
Get the number of unconnected buffers
To determine the number of unconnected buffers that are currently available,
configure a Message (MSG) instruction as follows.
On this tab For this item Type or choose
Configuration Message Type CIP Generic
Service Type Custom
Service Code 3
Class 304
Instance 1
Attribute 0
Source Element source_array where data type = SINT[4]
In this element Enter
source_array[0] 1
source_array[1] 0
source_array[2] 17
source_array[3] 0
Source Length (bytes) 4 (Write 4 SINTs.)
Destination Element destination_array where data type = SINT[10] (Leave all values = 0.)
destination_array[6] = current number of unconnected buffers
Communication Path 1, slot_number_of_controller
Get or set the number of
unconnected buffers
14 Rockwell Automation Publication 1756-PM012F-EN-P - October 2014
Seitenansicht 13
1 2 ... 9 10 11 12 13 14 15 16 17 18 19 ... 33 34

Kommentare zu diesen Handbüchern

Keine Kommentare