Seitenansicht 15
16 Rockwell Automation Publication IASIMP-QS028A-EN-P - July 2012
Chapter 1 Prepare the PowerFlex 40 Drive Hardware
2. Verify that a jumper is installed
between I/O terminals 01 and 11
on the drive.
The drive ships from the factory
with the jumper installed by
default.
3. If a jumper is not installed, install one before continuing.
4. Remove the terminal block cover to access the power connections.
5. Insert the 120/240V AC, V AC
COM, and chassis ground wires
and tighten the terminal screws.
6. Do not apply power to the drive.
Connect To
120/240V AC R/L1
V AC COM S/L2
Chassis ground
01 02 03 04 05
11 12 13 14 15
V/T2T/L3S/L2R/L1 U/T1 W/T3
BR+ BR-DC-
DC+