20 • Use graphic objects
20-7
• • • • •
Work with lists, trends, alarm banners, and numeric input objects
Use this button With this graphic object To do this
Pause button Trend Toggle a trend between pausing and automatic scrolling.
Next pen button Trend Change the vertical axis labels for a trend to the scale for
the next pen.
Backspace button Control list selector
Piloted control list
selector
Move the cursor back to the highlighted item in the list.
End button Lists and trends List—move to the bottom item in the list.
Trend—resume trend scrolling and move to the current
(latest) data in the trend.
Enter button Lists
Alarm list and alarm
banner
Select the item the cursor is pointing to.
Acknowledge the currently selected alarm.
Home button Lists and trends List—move to the top item in the list.
Trend—pause the trend and move to the earliest data in
the trend.
Move left / right buttons Trend, Diagnostics list Trend—Pause the trend and scroll to the left or right.
Diagnostics list—scroll the diagnostic message content
across the display to view the full content.
Move up / down buttons Lists, trends, and numeric
input objects
List—move up or down one item in the list.
Trend—scroll up or down to show higher or lower values
on the vertical scale.
Numeric input cursor point and Numeric Input Enable
button—ramp the value up or down.
Page up / down buttons Lists Move up or down one page in the list.
Acknowledge alarm
button
Alarm list
Alarm banner
Acknowledge and silence the selected alarm.
Alarm status mode
button
Alarm status list Change the type of alarms shown in the alarm status list,
from all alarms to active alarms to past alarms.
Clear alarm banner
button
Alarm banner Clear the alarm in the alarm banner without removing the
alarm from the alarm log file and alarm lists.
Diagnostics clear button Diagnostics list Remove the selected message from all diagnostics lists.