AutoMax ControlNet Module Page 77
Publication number DSMBCN-UM001B-EN-P February 2003
6. Select Device > Scanlist Configuration. Notice that the status
columns are not displayed.
7. Double-click a connection. On the Connection Properties, note that
three dashes are shown in the Status address field.
8. In the Status address field, specify the desired status offset and click
OK.
9. Repeat steps 7 and 8 for each connection.
10. Select File > Save.
11. Close the Scanlist Configuration Tool.
12. Select Device > Scanlist Configuration again. Notice that the status
columns are now displayed.
13. Verify that the status addresses displayed in the Status address
column are correct.
Tip: If any status offset values are displayed incorrectly, double-click a
connection and enter the correct value.
14. Select File > Save.
15. Select Device > Download to Device.