5-14
Document: 553634
(ICSTT-RM406F_EN_P) Issue: 089:
Troubleshooting and Maintenance Manual (AADvance
Controller)
2) Remove the blown fuse with a pair of long nosed pliers.
3) Insert a new fuse using the same long nosed pliers.
4) Close the fuse cover.
Install a New Termination Assembly
To install a new termination assembly, do the following.
Remove the I/O Module(s)
Remove each I/O module that uses the termination assembly:
1) Locate the head of the clamp screw on the front of the module. Use a broad
(8mm) flat blade screwdriver to turn the screw counterclockwise a quarter turn
(so the slot is vertical) to unlock the clamp.