Rockwell-automation AADvance Controller Troubleshooting and Maintenanc Bedienungsanleitung Seite 28

  • Herunterladen
  • Zu meinen Handbüchern hinzufügen
  • Drucken
  • Seite
    / 96
  • Inhaltsverzeichnis
  • LESEZEICHEN
  • Bewertet. / 5. Basierend auf Kundenbewertungen
Seitenansicht 27
3-6
Document: 553634
(ICSTT-RM406F_EN_P) Issue: 089:
Troubleshooting and Maintenance Manual (AADvance
Controller)
A module fault (below)
A fault the controller cannot isolate it to a single module. An example would be
the absence of every I/O module in a termination assembly group.
The System Healthy LED on each processor module will show red.
Module Fault
The controller indicates a module fault when it detects a fault and can isolate it to the hardware of a
particular module. The Healthy LED on the faulty module will show red and the System Healthy LED
on each processor module will also show red.
Channel Fault
The controller indicates a channel fault when it detects a fault and can isolate it to a hardware fault on
a specific channel of a single I/O module. The controller always reports a channel fault as a module
fault as well. This means that the Channel LED will show red, the Healthy LED of the I/O module will
show red and the System Healthy LED on each processor module will also show red.
Field Fault
The AADvance controller indicates a field fault when it detects a fault and can isolate it to a field
condition or a field device. Examples are an open circuit field connection or an out-of-range signal. The
Channel LED on the relevant I/O module will show amber.
Seitenansicht 27
1 2 ... 23 24 25 26 27 28 29 30 31 32 33 ... 95 96

Kommentare zu diesen Handbüchern

Keine Kommentare