(4) A A A Drive Current Ratings shown are only for Normal Duty, 0...1000 m altitude, and 0...40 ºC
ambient temperature.
Not all drive current ratings are available in all voltages. Refer to the PowerFlex 6000
Selection Guide.
a
Bulletin Number
Code Description
6000 All Drive Products
b
Service Duty/Altitude/Ambient Temperature Code
Code Type
• •
Service Duty (First Position)
A: Normal Duty
Z: Custom (Contact Factory)
• •
Altitude (Second Position)
A: 0...1000 m
(1)
B: 1001...2000 m
(2)
C: 2001...3000 m
(2)
Z: Custom (Contact Factory)
(1) 0...1000 m (• A B) is the only valid altitude for 50 ºC, as a standard supported option.
(2) Derating for altitude is 10% of the stated A
A A Drive Current Rating for 1001...2000 m, and
20% of the stated A
A A Drive Current Rating for 2001...3000 m.
(3) Derating for ambient temperature is 2.5% of the stated A
A A Drive Current Rating per degree
over 40 ºC.
• •
Ambient Temperature (Third Position)
A: 0...40 ºC
B: 0...50 ºC
(1)(3)
Z: Custom (Contact Factory)
c
A A A Drive Current Rating
(4)
Code Description Code Description
15 15 Amp 25 25 Amp
16 16 Amp 26 26 Amp
18 18 Amp 28 28 Amp
20 20 Amp 30 30 Amp
24 24 Amp 32 32 Amp
c (continued)
A A A Drive Current Rating
(4)
Code Description Code Description
33 33 Amp 112 112 Amp
36 36 Amp 120 120 Amp
40 40 Amp 125 125 Amp
41 41 Amp 138 138 Amp
45 45 Amp 140 140 Amp
48 48 Amp 150 150 Amp
50 50 Amp 160 160 Amp
54 54 Amp 168 168 Amp
56 56 Amp 180 180 Amp
60 60 Amp 192 192 Amp
63 63 Amp 200 200 Amp
66 66 Amp 225 225 Amp
71 71 Amp 250 250 Amp
75 75 Amp 280 280 Amp
80 80 Amp 300 300 Amp
84 84 Amp 315 315 Amp
90 90 Amp 350 350 Amp
96 96 Amp 380 380 Amp
100 100 Amp 420 420 Amp
108 108 Amp
Position
123456789
6000 A A A 41 M R 5 AL R 1...etc.
abcde fghi