Rockwell Automation Publication 193-UM015B-EN-P - June 2014 81
Protective Trip and Warning Functions Chapter 5
Full Load Amps Setting
FLA (Parameter 171) is one of two parameters that affect the E300 Electronic
Overload Relays thermal capacity utilization algorithm. The installer enters the
motors full-load current rating into this parameter.
Table 58 - FLA (Parameter 171)
FLA2 (Parameter 177) is provided for programming the high-speed FLA value in
two-speed motor applications. Activating FLA2 is described in Chapter 3
.
IMPORTANT
The Protection Fault State of Relay 0, Relay 1, Relay 2, Digital Module 1 Output
Relays, Digital Module 2 Output Relays, Digital Module 3 Output Relays, and
Digital Module 4 Output Relays are defined by the respective parameters:
Output PT00 Protection Fault Action (Parameter 304)
Output PT00 Protection Fault Value (Parameter 305)
Output PT01 Protection Fault Action (Parameter 310)
Output PT01 Protection Fault Value (Parameter 311)
Output PT02 Protection Fault Action (Parameter 316)
Output PT02 Protection Fault Value (Parameter 317)
Output Digital Module 1 Protection Fault Action (Parameter 322)
Output Digital Module 1 Protection Fault Value (Parameter 323)
Output Digital Module 2 Protection Fault Action (Parameter 328)
Output Digital Module 2 Protection Fault Value (Parameter 329)
Output Digital Module 3 Protection Fault Action (Parameter 334)
Output Digital Module 3 Protection Fault Value (Parameter 335)
Output Digital Module 4 Protection Fault Action (Parameter 340)
Output Digital Module 4 Protection Fault Value (Parameter 342)
FLA (Parameter 171)
Default Value
0.50 (0.5…30 A Sensing Modules)
6.00 (6…60 A Sensing Modules)
10.00 (10…100 A Sensing Modules)
20.00 (20…200 A Sensing Modules)
Minimum Value 0.50
Maximum Value 65535.00
Parameter Type UDINT
Size (Bytes) 4
Scaling Factor 100
Units Amps