68 Rockwell Automation Publication 193-UM015B-EN-P - June 2014
Chapter 3 System Operation and Configuration
Output Pt00 Assignment (Parameter 202)
Output Pt00 Assignment (Parameter 202) allows the user to assign this relay
output for the following functions:
Table 45 - Output Pt00 Assignment (Parameter 202)
Output Pt01 Assignment (Parameter 203)
Output Pt01 Assignment (Parameter 203) allows the user to assign this relay
output for the following functions:
Table 46 - Output Pt01 Assignment (Parameter 203)
Value Assignment Description
0 Normal Function as a relay output
1Trip Relay
Function as a normally closed contact until the E300 is in a tripped state in which the relay
opens. The Trip Relay remains open until a trip reset is issued.
2Control Relay
Function as a combination Normal and Trip Relay. The Control Relay is in a normally open
state until the relay is commanded to close by communications or via a DeviceLogix
program. When the E300 enters into a tripped state the Control Relay opens and remains
open until a trip reset is issued.
3Trip Alarm
Function as a normally open contact until the E300 is in a tripped state in which the relay
closes. The Trip Alarm remains closed until a trip reset is issued.
4 Warning Alarm
Function as a normally open contact until the E300 is in a protection warning state in which
the relay closes. The Warning Alarm remains closed until the protection warning clears.
Value Assignment Description
0 Normal Function as a relay output
1Trip Relay
Function as a normally closed contact until the E300 is in a tripped state in which the relay
opens. The Trip Relay remains open until a trip reset is issued.
2Control Relay
Function as a combination Normal and Trip Relay. The Control Relay is in a normally open
state until the relay is commanded to close by communications or via a DeviceLogix
program. When the E300 enters into a tripped state the Control Relay opens and remains
open until a trip reset is issued.
3Trip Alarm
Function as a normally open contact until the E300 is in a tripped state in which the relay
closes. The Trip Alarm remains closed until a trip reset is issued.
4 Warning Alarm
Function as a normally open contact until the E300 is in a protection warning state in which
the relay closes. The Warning Alarm remains closed until the protection warning clears.