Introduction to PanelBuilder
Chapter 1
1-12
PLC5/11, 5/15, 5/20, 5/25, 5/30, 5/40, 5/60 and 5/250 Processors
You can connect one or more PanelView terminals directly to a PLC-5
Remote I/O Port (in Scanner Mode) along with other I/O racks. If the
PLC-5 Remote I/O Port is used in the adapter mode, one or more
PanelView terminals can be connected to that PLC-5 along with other I/O
racks via a 1771-SN I/O Subscanner Module.
All Series C Rev A and later terminals can communicate at 230.4K baud
with any PLC-5 capable of supporting that baud rate.
If you are using a PLC-5/15 with partial rack addressing and block
transfers, you must use PLC-5/15 series B, revision J or later.
Table 1.B
Rack
Address Ranges of the PLC5 Family
PLC5/11 Rack 3 only
PLC5/15 13 (octal)
PLC5/20 13 (octal)
PLC5/25 17 (octal)
PLC5/30 17 (octal)
PLC5/40 117 (octal)
PLC5/60 127 (octal)
PLC5/250 037 (octal)
PLC5/10 Processor
One or more PanelView terminals can be connected to this processor along
with other I/O racks via the 1771-SN I/O Subscanner Module.
PLC3 and PLC3/10 Processors
One or more PanelView terminals can be connected directly to a PLC-3 or
PLC-3/10 remote I/O Scanner along with other I/O racks.
If you are using a 1775-S4A Remote Scanner /Distribution panel, you must
use Series B or higher.