ControlNet Communications 17
Publication 2711-6.10
Terminal Alert Codes
These messages appear on the terminal screen as DC Error = xx and
alert the user to a particular condition. If you should get an alert
number that is not listed here, contact Allen-Bradley for technical
support.
Alert Number Alert Type Indicates: Recommended Action(s):
9000 Critical fault Interface startup failed. Contact Allen-Bradley for technical support.
9003 Critical fault CIP S/N is not valid. Contact Allen-Bradley for technical support.
9004 Critical fault Out of buffers Contact Allen-Bradley for technical support.
9010 Critical fault
Invalid target node, target node is the same as the
PV, or larger than UMAX.
Check node addresses of all devices on the
network including the PanelView terminal.
9012
Communications
Warning
ControlNet object received a reset request. Contact Allen-Bradley for technical support.
9014 Critical fault A fatal CPU fault occurred. Contact Allen-Bradley for technical support.
9015 Critical fault A ControlNet hardware fault occurred. Contact Allen-Bradley for technical support.
9016 Critical fault RAM verification failed at startup. Contact Allen-Bradley for technical support.
9017 Critical fault CRC verification failed at startup. Contact Allen-Bradley for technical support.
9018 Critical fault A critical internal error occurred. Contact Allen-Bradley for technical support.
9019 Critical fault An internal fault occurred.
Reset terminal, if problem occurs again,
contact Allen-Bradley for technical support.
9020 Critical fault An internal fault occurred.
Reset terminal. If problem occurs again,
reload application. If problem persists, contact
Allen-Bradley for technical support.
Communication Status and Terminal Alert Messages
Message Alert Type Indicates: Recommended Action(s):
PanelView off–line.
Communications
warning
PanelView off–line. Check communication connections.
Initial write failed.* Reminder
Write to Logic Controller on Startup was configured
and on powerup, the PanelView could not write
initial values to a node’s data table address.
or
Write to Logic Controller on Startup was not
configured and the PanelView was unable to write
a logic controller. Note: The error message is only
displayed on the first write attempt.
Check/define data table address in the logic
controller.
Check communication connections and node
configuration in the application.
Write fail.*
Communications
warning
PanelView is communicating with logic controller.
The data table address does not exist.
Check/define data table address in the logic
controller.
Write timeout.*
Communications
warning
PanelView is not communicating with the logic
controller.
Check communication connections and node
configuration in the application.
Read fail.*
Communications
warning
PanelView is communicating with logic controller.
The data table address does not exist.
Check/define data table address in the logic
controller.
Read timeout.*
Communications
warning
PanelView is not communicating with the logic
controller.
Check communication connections and node
configuration in the application.
* These messages display the node number associated with the message.