Troubleshooting 8-5
The following diagnostic items can be accessed using DriveExplorer
(version 3.01 or higher).
Net B Status Indicator
Status Cause Corrective Actions
Off The adapter is not
powered, or is not
transmitting on the
network.
If Net A indicator is off:
• Securely connect the adapter to the drive
using the Internal Interface (ribbon) cable and
to the network using an Ethernet cable.
• Correctly connect the Ethernet cable to the
Ethernet connector.
• Set a unique IP address using a BOOTP
server or by disabling BOOTP and using
adapter parameters.
If Net A indicator is solid red:
• Configure the adapter to use a unique IP
address and cycle power.
If Net A indicator is flashing red:
• Check the IP address in the adapter and
scanner.
• Ping the adapter.
Normal condition if the adapter is idle.
Flashing
Green
The adapter is transmitting
on the network.
No action required.
Adapter Diagnostic Items in Single Drive Mode
No. Name Description
1 Reserved
2 Logic Cmd Logic Command being transmitted to the drive by the adapter.
3 Reference Reference being transmitted to the drive by the adapter.
4 Reserved
5 Logic Sts Logic Status being received from the drive by the adapter.
6 Feedback Feedback being received from the drive by the adapter.
7 – 22 Reserved
23 DSI Overrun Errs The number of DSI receive overrun errors.
24 DSI Framing Errs The number of DSI receive framing errors.
25 DSI CRC Errs The number of DSI receive CRC errors.