Troubleshooting 8-3
MOD Status Indicator
Status Cause Corrective Action
Off The adapter is not powered or
not properly connected to the
drive.
Securely connect the adapter to the drive
using the Internal Interface (ribbon) cable.
Apply power to the drive (or adapter if
mounted in a DSI External Comms Kit).
Flashing
Red
The adapter has failed the
firmware test.
Cycle power to the drive (or adapter if
mounted in a DSI External Comms Kit).
If cycling power does not correct the
problem, the adapter parameter settings
may have been corrupted. Reset defaults
and reconfigure the adapter.
If resetting defaults does not correct the
problem, flash the adapter with the latest
firmware release.
Solid
Red
The adapter has failed the
hardware test.
Cycle power to the drive (or adapter if
mounted in a DSI External Comms Kit).
Replace the adapter.
Flashing
Green
The adapter is operational, but
is not transferring I/O data.
Place the scanner in RUN mode.
Program the controller to recognize and
transmit I/O to the adapter.
Configure the adapter for the program in
the controller.
Solid
Green
The adapter is operational and
transferring I/O data.
No action required.