Troubleshooting 7-3
(1)
Only visible when drive cover is open.
Bus Active (BA) Status Indicator
Status Cause Corrective Actions
Off Bus not active.
Set master to start data transmission.
Solid Green Bus active, exchanging
data.
No action.
Flash Green Bus active, but no data
exchange.
Set master to start data transmission.
Bus Voltage (UL) Status Indicator
(1)
Status Cause Corrective Actions
Off Bus voltage is not OK.
Securely connect the adapter to the drive
using the Internal interface cable
Apply power to the drive.
Solid Green Bus active.
No action.