Configuring the Interbus Scanner 4-9
The gray PCP icons represent each PowerFlex 70 drive. The first
PowerFlex 70 has a Device Number of 1.0 and the second has a Device
Number of 2.0.
13. Right-click on the SST-IBS-SLC scanner and select Process Data.
This shows the Interbus I/O mapping for each device on the network,
as shown in Figure 4.12
.
Figure 4.12 Example Interbus I/O Mapping
In the example, the length is 144 bits (9 words) because the 20-COMM-I
was previously configured for the maximum I/O configuration (See
Chapter 3, Setting the I/O Configuration on page 3-3. Depending on
your application needs, this length may be less.