Seitenansicht 11
12 ArmorBlock MaXum 4 Output Module Series B
Publication 1792D-IN040B-EN-P - September 2000
4 Output Module - Cat. No. 1792D-OB4D
Environmental Conditions
Operational Temperature
Storage Temperature
Relative Humidity
Shock Operating
Non-operating
Vibration
-25 to 60
o
C (-13 to 140
°
F)
-25 to 80
o
C (-13 to 176
°
F)
Up to 100%
30g peak acceleration, 11 (+1) ms pulse width
50g peak acceleration, 11 (+1) ms pulse width
Tested 10g @ 10-500 Hz per IEC 68-2-6
Conductors Publication DN-6.7.2
Enclosure Meets or exceeds IP67
Agency Certification
(when product is marked)
CSA certified
CSA Class 1, Division 2, Groups A, B,
C, D certified
UL listed
CE marked for all applicable directives