Seitenansicht 9
10 ArmorBlock MaXum 4 Output Module Series B
Publication 1792D-IN040B-EN-P - September 2000
The following table describes network and module status indicators.
The following table describes logic status indicators.
The following table describes Auxiliary power indicator.
The following table describes I/O status indicators.
Net/Mod Status Indicator
Indicator Status
Off No power or auto bauding
Flashing Green/Off On line but not connected
Solid Green On line, link OK, connected
Flashing Red Recoverable fault - module configuration error
I/O connection fault - one or more I/O connections in the timed-out state
Solid Red Unrecoverable fault
Communication failure - duplicate node address present or incorrect
baud rate
Green to Red to Off At powerup only - LED test
Logic Status Indicators
State Status
Off Logic is disabled
Solid Green Logic is enabled
Flashing Green Local forces are applied and local logic is enabled
Auxiliary Power
Indication Status
None No Auxiliary Power
Green
Solid Auxiliary Power Present
I/O Status Indicators
Function Module Status Indicator Point Indicator Condition
Outputs Green
Green
Module Status blink red
Module Status blink red
Module Status blink red
Module Status blink red
None
Yellow
Orange
Red
Orange
Red
Output not energized
Output energized
Output shorted-auto restart
Output shorted-latching
Output no load-auto restart
Output no load-latching