32 CompactBlock Distributed I/O on Remote I/O Series D
Publication
1791R-IN002B-EN-P - August 2003
Specifications
Comm Status Indicator
Indication: Status:
Off Communication not established
Green Communication established
Flashing Green Processor in Program mode
I/O Status Indicators
Function: LED Color: Module
Illumination:
Condition:
Outputs Each output:
Yellow
None
Yellow
Output not energized
Output energized
Inputs Each Input:
Yellow
None
Yellow
No valid input
Valid input
Sinking or Sourcing Input Specifications
Inputs per block groups of 4 or 8
Off-state Voltage 5V dc maximum
On-state Voltage 30V dc @ 40×C maximum
25V dc @ 60×C maximum
10V dc minimum
Off-state Current 1.5mA minimum
On-state Current 11mA @ 30V dc maximum
2mA @ 10V dc minimum
Sinking or Sourcing Output Specifications
Outputs per block groups of 4 or 8
On-state Voltage Range 10 - 30V dc
On-state Voltage Drop 0.5V dc @ rated current
On-state Current 0.5A maximum
Off-state Leakage 1.0mA maximum
Module Current (per output) 0.5A maximum