22 CompactBlock Distributed I/O on Remote I/O Series D
Publication
1791R-IN002B-EN-P - August 2003
Communicate With the 1791R Module
Determine the Baud Rate for Yo u r R e m ote I /O C o n ne c t io n
Use the DIP switches to set the baud rate before you power up the module.
Refer to the following table for baud rate specifications.
I/O Image Word/Bit Definitions
The smallest portion of a scanners I/O image that can be allocated to a single
Remote I/O device is two logical groups or 1/4 logical rack. A device’s
starting group must begin at even group numbers (0, 2, 4, or 6). See your
scanner documentation for further details.
All combinations of 1791R base and expansion modules will fit in the space
allocated by 1/4 logical rack, except for the 1791D-N4CV2X analog module,
which fits in a 3/4 rack.
I/O images for 1791 Remote I/O base modules follow.
Baud Rate Cable Length
57.6KBPS 3048m
115.2KBPS 1524m
230.4KBPS 762m
16B0
17 16 15 14 13 12 11 10 7 6 5 4 3 2 1 0
Input
Image
In
15
In
14
In
13
In
12
In
11
In
10
In
9
In
8
In
7
In
6
In
5
In
4
In
3
In
2
In
1
In
0
Input
Image
Reserved
Output
Image
Reserved
Output
Image
Reserved
Kommentare zu diesen Handbüchern