2 and 4–Wire RTD SensorsE–2
    
Three–wire and 4–wire sensors compensate for lead resistance error.
Their schematic representation is shown below. The amount of error
elimination depends upon the difference between the resistance
values of the lead wires. The closer the resistance values are to each
other, the greater the amount of error that is eliminated.
Connections for 3 and 4–Wire Sensors
3-Wire Sensor
 
4-Wire Sensor
There are several ways to insure that the lead resistance values match
as closely as possible. They are:
use heavy gauge wire (16–18 gauge)
keep lead distances less than 1000 feet
use quality cable that has a small tolerance impedance rating.