Publication 1769-RM016A-EN-P - July 2006
74 Module Addressing and Configuration with MicroLogix 1500
Output Image
The module's output image file represents directed output states and virtual
input states. Output word 0 holds the directed states for the module's outputs
(OUT0 through OUT3) when any of the outputs are configured for direct
control mode. Output word 1 holds the states of the module's virtual inputs
(V0 through V7) can be used as Boolean operands when any of the module's
outputs are configured for Boolean Control mode.
For example, to set the state of virtual input V2 of a module when it is in slot
3, use address O:3.1/2.
TIP
The end cap does not use a slot address.
O:3.1/2
Output File Type
Slot
Word
Bit
Bit Delimiter
Word Delimiter
Element Delimiter
0123
MicroLogix 1500
Compact I/O
Compact I/O
Compact I/O
End Cap
Slot Number
Seitenansicht 73