Rockwell-automation 1769-BOOLEAN Compact I/O Module Reference Manual Bedienungsanleitung Seite 66

  • Herunterladen
  • Zu meinen Handbüchern hinzufügen
  • Drucken
  • Seite
    / 98
  • Inhaltsverzeichnis
  • LESEZEICHEN
  • Bewertet. / 5. Basierend auf Kundenbewertungen
Seitenansicht 65
Publication 1769-RM016A-EN-P - July 2006
66 1769-BOOLEAN Module Specifications
Nominal Impedance 2.0 kohm @ 24V dc
2.3 kohm @ 30V dc
IEC Input Compatibility Type 3
Input Point to Bus (CompactBus)
Isolation
Verified by one of the following dielectric tests: 1200V ac for 1
s or 1697V dc for 1 s
75V dc working voltage (IEC Class 2 reinforced insulation)
(1)
Sinking Input - Sink describes the current flow between the I/O module and the field device. Sinking I/O circuits are
driven by a current sourcing field device. Field devices connected to the positive side (+V) of the field supply are
sourcing field devices. Europe: DC sinking input and sourcing output module circuits are the commonly used options.
Attribute Value