6-6 EMail Messages (Node 50 to 99)
2. Open the message instruction and enter the appropriate
variables. The variables are described in Table 6.2.
Table 6.2 Message Instruction Variables for Sending an Email Message
Variable Setting
This Controller Parameters:
Communication Command 485CIF/PLC2
Data Table Address Any valid string, such as ST25:21 as shown below.
Size in Elements 1
Channel The RS-232 communication channel that is connected to the
ENI/ENIW, typically 0 or 1.
Target Device Parameters:
Message Timeout Increase this value to 10 or greater to avoid MSG timeouts.
Data Table Offset Always 0.
Local Node Addr (dec). This is the destination node address. Nodes 50 to 99 send
email messages; nodes 150 to 199 configure the email
address.
Local/Remote Always Local.