Rockwell-automation 1756-Lx_Mx ControlLogix Controller and Memory Boar Bedienungsanleitung Seite 39

  • Herunterladen
  • Zu meinen Handbüchern hinzufügen
  • Drucken
  • Seite
    / 52
  • Inhaltsverzeichnis
  • LESEZEICHEN
  • Bewertet. / 5. Basierend auf Kundenbewertungen
Seitenansicht 38
ControlLogix® Controller and Memory Board 39
Publication
1756-IN101J-EN-P - November 2004
Choose the Operating Mode of the Controller
Important All modes send and receive data in response to a message from another controller.
All modes produce and consume tags.
No
Do you want to prevent
RSLogix 5000 software from
changing the mode?
Do you want to execute the
logic in the controller?
Do you want the logic to
control the output devices?
Turn the keyswitch to PROG
and then to REM
(Remote Program mode).
Turn the keyswitch to PROG
(Program mode).
Turn the keyswitch to RUN
and then to REM
(Remote Run mode).
No
Yes
Do you want to prevent
RSLogix 5000 software from:
changing the mode
downloading a project
performing online edits
Turn the keyswitch to RUN
(Run mode).
No
Yes
Do you need to schedule a
ControlNet network?
No
Yes
Outputs revert to their configured state for Program mode.A
This includes Message (MSG) instructions.
B
No
1. Turn the keyswitch to REM.
2. Go online with
RSLogix 5000 software and
choose Test mode.
Yes
B
A
A
A
Yes
Seitenansicht 38
1 2 ... 34 35 36 37 38 39 40 41 42 43 44 ... 51 52

Kommentare zu diesen Handbüchern

Keine Kommentare