Analog Input Modules
(T7420A, AF)
PD
-
7023
Mar
-
06
23
Figure
14
. I/O Extender Connections for Differential Analog Input Calibration.
Within each pair of jumper posts, make sure that you connect
the voltage source to the jumper posts nearest the front of the
I/O extender. Do not make any connections to the jumper
posts nearest the I/O chassis backplane
these connect to the
actual field wiring attached to the I/O slot terminals on the I/O
chassis.
Calibration Steps
1.
Remove the module to be calibrated from the I/O chassis.
2.
Install the I/O extender module into the slot from which
the module was removed.
3.
Remove the jumpers (if installed) labeled CH1 through
CH16 from the I/O extender module.
Important!