Guarded analog output modules provide 4 to 20 mA current
outputs for a maximum of six user loads per module. These
modules are called Guarded because the module's dual
-
redundant design ensures that no single fault within a
module will inadvertently change an output's signal. The
module's triplicated Safetybus interface ensures that no
Regent system failure will inadvertently affect the output
signal. Extensive fault detection and annunciation of critical
redundant circuits ensures the modules will continue to
operate in a fail
-
safe mann
er.
Features
·
Six 4 to 20 mA output circuits.
·
Dual, high resolution, 12
-
bit D/A converters per output.
·
Fault tolerant operation when connected in parallel with
another module of the same type.
·
Hot
-
replaceable.
·
Comprehensive self
-
testing of all critical circuits.
·
Front panel indicators on each module s
how active/fault,
shutdown, and on status.
·
2500 volt minimum electrical isolation between field and logic
circuits.
·
TÜV certified, Risk Class 5, non
-
interfering.
Two Guarded output modules can be connected in parallel to
obtain fault tolerant control of current to the loads. In this
parallel module configuration, either module can be removed
and replaced while the other Guarded module continues to
control the loads without interruption.
Seitenansicht 0
1 2 3 4 5 6 ... 27 28

Inhaltsverzeichnis

Seite 1 - ICS Regent

ICS Regent® PD-6026 Industrial Control Services 1 Guarded Analog Output Modules 4 to 20 mA (T3480) Issue 1, March, 06 Guarded analog output modules

Seite 2 - Module Operation

Guarded Analog Output Modules (T3480) 10 Industrial Control Services Figure 6. Fault Tolerant Module Wiring.

Seite 3

Guarded Analog Output Modules (T3480) PD-6026 Mar-06 11 Effects of Open Circuit Field Wiring When a Guarded analog output module is controlling t

Seite 4 - Front Panel Indicators

Guarded Analog Output Modules (T3480) 12 Industrial Control Services While in this mode the remaining output loads that have healthy field wiring

Seite 5

Guarded Analog Output Modules (T3480) PD-6026 Mar-06 13 Figure 7. Installing Slot Keys. Configuration Each output module is configured using

Seite 6

Guarded Analog Output Modules (T3480) 14 Industrial Control Services 1) Set the Module Type: Position the cursor on the module slot you wish to d

Seite 7

Guarded Analog Output Modules (T3480) PD-6026 Mar-06 15 Figure 9. Defining an Analog Output Point. Name Also called the tag name, this is the n

Seite 8 - Field Wiring

Guarded Analog Output Modules (T3480) 16 Industrial Control Services Programming Outputs are controlled by writing application programs that solve

Seite 9

Guarded Analog Output Modules (T3480) PD-6026 Mar-06 17 control logic, you maintain the full resolution of the analog output (1 part in 4096) and

Seite 10 - Industrial Control Services

Guarded Analog Output Modules (T3480) 18 Industrial Control Services · Potentiometer adjustment tool. · Phillips screwdriver · I/O module extender

Seite 11

Guarded Analog Output Modules (T3480) PD-6026 Mar-06 19 Figure 12. Guarded Analog Output Module Calibration Potentiometer Locations. The I/O

Seite 12 - Fault Mode Jumper

Guarded Analog Output Modules (T3480) 2 Industrial Control Services Module Operation A block diagram of the Guarded analog output module is shown

Seite 13 - Configuration

Guarded Analog Output Modules (T3480) 20 Industrial Control Services Figure 13. I/O Extender Connections for Guarded Analog Output Calibration

Seite 14

Guarded Analog Output Modules (T3480) PD-6026 Mar-06 21 4. Connect the six precision resistors to the I/O extender jumper posts as shown in Figur

Seite 15

Guarded Analog Output Modules (T3480) 22 Industrial Control Services these steps as there may be some interaction between the gain and offset adju

Seite 16 - Programming

Guarded Analog Output Modules (T3480) PD-6026 Mar-06 23 the module must be connected (using the I/O extender) to an I/O chassis of an operational

Seite 17 - Calibration Procedure

Guarded Analog Output Modules (T3480) 24 Industrial Control Services Figure 14. Location of Test Points for Latent Fault Testing. Testing Step

Seite 18 - Important!

Guarded Analog Output Modules (T3480) PD-6026 Mar-06 25 4. Connect the six termination resistors to the I/O extender jumper posts as shown in Fig

Seite 19

Guarded Analog Output Modules (T3480) 26 Industrial Control Services fault (green Activity LED turns off and the red Fault LED turns on). 11. Disc

Seite 20

Guarded Analog Output Modules (T3480) PD-6026 Mar-06 27 safety of the process should not be dependent on the operations of the guarded analog out

Seite 21

Guarded Analog Output Modules (T3480) 28 Industrial Control Services Electromagnetic Interference • IEC 801 Part 2 - Electrostatic Discharges • IE

Seite 22

Guarded Analog Output Modules (T3480) PD-6026 Mar-06 3 The combination of redundant interface circuits, D/A converters, and comparison of drive

Seite 23

Guarded Analog Output Modules (T3480) 4 Industrial Control Services shunting all six output channel signal outputs to AGND via the diode matrix.

Seite 24

Guarded Analog Output Modules (T3480) PD-6026 Mar-06 5 unit is set to shutdown, the red SHUTDOWN indicator will turn on when the communications

Seite 25

Guarded Analog Output Modules (T3480) 6 Industrial Control Services Figure 2. Guarded Analog Output Module.

Seite 26 - Safety Considerations

Guarded Analog Output Modules (T3480) PD-6026 Mar-06 7 Application Guarded analog output modules are suited for high integrity control of analog

Seite 27 - Specifications

Guarded Analog Output Modules (T3480) 8 Industrial Control Services Figure 4. Fault Tolerant Configuration. Field Wiring Field wiring termina

Seite 28

Guarded Analog Output Modules (T3480) PD-6026 Mar-06 9 Figure 5. Fail Safe Field Wiring.