Rockwell-automation T3464 ICS Regent AC Guarded Digital Output Module Bedienungsanleitung

Stöbern Sie online oder laden Sie Bedienungsanleitung nach Ausrüstung Rockwell-automation T3464 ICS Regent AC Guarded Digital Output Module herunter. Rockwell Automation T3464 ICS Regent AC Guarded Digital Output Module User Manual Benutzerhandbuch

  • Herunterladen
  • Zu meinen Handbüchern hinzufügen
  • Drucken
  • Seite
    / 22
  • Inhaltsverzeichnis
  • LESEZEICHEN
  • Bewertet. / 5. Basierend auf Kundenbewertungen
Seitenansicht 0
ICS Regent
®
PD
-
6021
Industrial Control Services
1
AC Guarded Digital Output Module
110 VAC
(T3464)
Issue 1,
March, 06
AC Guarded digital output modules provide guarded
switching of user
-
supplied 110 AC voltages to a maximum of
sixteen field loads. These modules are called Guarded
because no single fault within a module will inadvertently
apply power to an output. Extensive fault detection and
critical redundant circuits ensure that the module operates in
a fail
-
safe manner.
Features
·
Sixteen Guarded output circuits configured as two separately
powered groups of eight circuits each.
·
Fault tolerant operation when connected in parallel with
another module of the same type.
·
Hot
-
replace
able.
·
100% self
-
test of all critical circuits.
·
Zero
-
cross load switching.
·
Individual front panel indicators on each module show
active/fault and output on/off status (field side). A diagnostic
message display provides additional status indicators.
·
Fuses accessible from front panel.
·
2500 volt minimum electrical isolation between field and l
ogic
circuits.
·
TÜV certified, Risk Class 5, see Safety Considerations.
Two Guarded output modules can be connected in parallel to
obtain fault tolerant control of power to loads. In this parallel
module configuration, either module can be removed and
Seitenansicht 0
1 2 3 4 5 6 ... 21 22

Inhaltsverzeichnis

Seite 1 - ICS Regent

ICS Regent® PD-6021 Industrial Control Services 1 AC Guarded Digital Output Module 110 VAC (T3464) Issue 1, March, 06 AC Guarded digital output mod

Seite 2 - Module Operation

AC Guarded Digital Output Module (T3464) 10 Industrial Control Services Fault Tolerant Configuration For fault tolerant operation, two Guarded mod

Seite 3

(T3464) AC Guarded Digital Output Module PD-6021 Mar-06 11 Figure 5. Fault Tolerant Configuration with Redundant Actuators. Field Wiring Fiel

Seite 4 - Testing and Diagnostics

AC Guarded Digital Output Module (T3464) 12 Industrial Control Services Figure 6. Fail-Safe Field Wiring.

Seite 5

(T3464) AC Guarded Digital Output Module PD-6021 Mar-06 13 Figure 7. Fault Tolerant Field Wiring.

Seite 6 - Front Panel

AC Guarded Digital Output Module (T3464) 14 Industrial Control Services Fault Mode Jumper The fault mode jumper is located behind the ID switch co

Seite 7

(T3464) AC Guarded Digital Output Module PD-6021 Mar-06 15 Figure 8. Installing Slot Keys. Configuration Each output module is configured usi

Seite 8 - Application

AC Guarded Digital Output Module (T3464) 16 Industrial Control Services 1) Set the Module Type: Position the cursor on the module slot you wish t

Seite 9 - Safe Configuration

(T3464) AC Guarded Digital Output Module PD-6021 Mar-06 17 Name Also called the tag name, this is the name used in the application program to ref

Seite 10 - Actuators

AC Guarded Digital Output Module (T3464) 18 Industrial Control Services To program fault tolerant outputs two output coils driven by the same cont

Seite 11 - Field Wiring

(T3464) AC Guarded Digital Output Module PD-6021 Mar-06 19 Table 3. Initialization Sequence. Step Display Description 1 8.8.8.8. Display test.

Seite 12 - Industrial Control Services

AC Guarded Digital Output Module (T3464) 2 Industrial Control Services replaced while the other Guarded module continues to control the loads wit

Seite 13

AC Guarded Digital Output Module (T3464) 20 Industrial Control Services Table 4. Operating Diagnostic Messages. Display Description AC AC quality

Seite 14 - Fault Mode Jumper

(T3464) AC Guarded Digital Output Module PD-6021 Mar-06 21 Load Current (maximum) 1 amp maximum per output 0° to 40° C, derated linearly to 0.5 a

Seite 15 - Configuration

AC Guarded Digital Output Module (T3464) 22 Industrial Control Services Isolation 2500 volts minimum (field wiring to control logic) 2500 volts mi

Seite 16

(T3464) AC Guarded Digital Output Module PD-6021 Mar-06 3 the TRIAC will be de-energized. If the TRIAC itself fails shorted when commanded off,

Seite 17 - Programming

AC Guarded Digital Output Module (T3464) 4 Industrial Control Services Table 1. Output States After Switch Failure. Case Commanded Output Sta

Seite 18 - Maintenance

(T3464) AC Guarded Digital Output Module PD-6021 Mar-06 5 module error indication at the processor modules and a module fault indication at the

Seite 19

AC Guarded Digital Output Module (T3464) 6 Industrial Control Services the output switch's ability to conduct current (through an internal d

Seite 20 - Specifications

(T3464) AC Guarded Digital Output Module PD-6021 Mar-06 7 Figure 2. AC Guarded Output Module.

Seite 21

AC Guarded Digital Output Module (T3464) 8 Industrial Control Services Diagnostic Message Display This four-digit display provides additional fau

Seite 22

(T3464) AC Guarded Digital Output Module PD-6021 Mar-06 9 current flows through the neutral wire, so it is important to size both the line and n

Kommentare zu diesen Handbüchern

Keine Kommentare