Publication 2711P-QS001A-EN-P - October 2007 47
Review Unsupported Features and Implement Workarounds for Migration Issues Chapter 6
Replacing Scrolling List
Objects
Scrolling list objects in PanelBuilder 1400e software consists of a
cursor list and one or more object lists. The operator can move
through a maximum of 999 items within these object lists.
Scrolling lists can multiplex PLC output data to the PanelView ‘e’
terminal, minimizing the ladder logic required to display and edit
large amounts of data.
FactoryTalk View ME software does not support scrolling list objects.
but does provide replacement objects to perform the same operations.
Replacement Objects for Scrolling List Objects
Replace this PanelView ‘e’ object With this FactoryTalk View ME object See
Cursor List • Piloted Control List Selector
• Key buttons
• Terminal function keys
• Page 48
• Page 53
• Page 55
Multistate Indicator Object List Multistate Indicator Page 56
Local Message Object List Local Message Page 60
Numeric Data Display Object List Numeric Data Display Page 64