Rockwell-automation MDO32BNS 32-Channel Digital Output Module Bedienungsanleitung Seite 15

  • Herunterladen
  • Zu meinen Handbüchern hinzufügen
  • Drucken
  • Seite
    / 18
  • Inhaltsverzeichnis
  • LESEZEICHEN
  • Bewertet. / 5. Basierend auf Kundenbewertungen
Seitenansicht 14
MDO32BNS October
200
5
Issue 7
15
Triguard
SC300E MDO32BNS 32
-
Channel Digital Output Module
SERVICING
SCOPE
System
repair
is
by
mod
ule
replacement.
Faulty
modules
are
not
repairable
in
the
field;
they
should
be
replaced
by
new
modules
and
returned
for
repair.
CAUTION
1
The
module
contains
components
that
may
be
electrostatically
sensitive.
It
should
be
transported
and
stored
in
its
original
packaging
material.
CAUTION
2
Before
fitting
a new
module
ensure
that
the
setting
of
all
three
links
is
the
same
as
that
on
the
old
module.
DIAGNOSIS
The
TriBuild
workstation
is
used
for
fault
diagnosis.
In
the
case
of
an
Input/Output
fault
the
Health
LED
on
the
faulty
module
will
be
extinguished
Preparation
To
ascertain
whether
the
chassis
I/O
slot
containing
the
faulty
module
has
been
allocated
a
hot
repair
partner
use
one
of
the
following
methods:
Check
the
system
drawings
Check
the
chassis
wiring
configuration
Use
the
I/O
chassis
configuration
report
on
the
TriBuild
workstation.
Where
there
is
a Hot
Repair
partner
allocation,
use
the
‘dual
-
slot
hot
repair’
procedure;
otherwise
use
the
‘single
-
slot
hot
repair’
procedure.
Configuration
The
only
configuration
necessary
is
the
correct
setting
of
the
three
links
which
are
shown
in
Figure
1
-
1.
Ensure
that
the
link
configuration
on
the
new
module
is
the
same
as
that
on
the
old
module.
Seitenansicht 14
1 2 ... 10 11 12 13 14 15 16 17 18

Kommentare zu diesen Handbüchern

Keine Kommentare