
16 Rockwell Automation Publication IASIMP-QS029A-EN-P - February 2012
Chapter 1 Prepare the PowerFlex 40 Drive Hardware
4. Remove the terminal block
cover to access the power
connections.
The drive can use any of the
following inputs:
• 120V AC single phase
• 230V AC single phase
• 230V AC three phase
• 480V AC three phase
In this quick start, you use
120VAC single phase.
5. Connect the AC power
conductors to the drive terminals as described in the following table and tighten the screws.
For complete information on wiring a PowerFlex 40 drive, see the PowerFlex 40 Adjustable
Frequency AC Drive User Manual, publication 22B-UM001.
Table 2 - 120/230V AC Single Phase Connections
Connect To
120/240V AC L1 R/L1
V AC COM L2 S/L2
Chassis ground
V/T2T/L3S/L2R/L1 U/T1 W/T3
BR+ BR-DC-
DC+
Kommentare zu diesen Handbüchern