Rockwell-automation GV3000/SE Operator Interface Module (OIM) User Gui Bedienungsanleitung Seite 66

  • Herunterladen
  • Zu meinen Handbüchern hinzufügen
  • Drucken
  • Seite
    / 112
  • Inhaltsverzeichnis
  • FEHLERBEHEBUNG
  • LESEZEICHEN
  • Bewertet. / 5. Basierend auf Kundenbewertungen
Seitenansicht 65
Troubleshooting the Drive Using the OIM
7-7
Step 2. If the DRIVE READY indicator is off, the drive is not ready to start. If this is
the case, move the cursor to “Why is the drive not ready?” and press .
The screen shows possible explanations of why the drive is not ready. If the
symbol is displayed, more information is available. Press to read the
rest of the screen. Table 7.1 lists all possible responses.
Step 3. Press to exit the screen.
Step 4. Press again at the Diagnostics Menu to return to program or monitor
mode.
7.5 Clearing a Programming Error Screen
Programming errors occur if you select an option that is not valid, such as attempting
to set a read-only parameter. These errors do not affect drive operation and are not
logged. To remove the programming error message, press .
Table 7.1 – Possible OIM Responses to “Why is the Drive Not Ready?”
Display Description
PRE-CHARGE IS NOT READY The DC bus is not within required tolerance.
FP STOP ACTIVE The front-panel STOP key is asserted.
SERIAL STOP ACTIVE The serial port (CS3000) stop input is
asserted.
ACTIVE CS STOP ACTIVE The active control source stop input is
asserted.
DRIVE NOT IDENTIFIED The Power Module has not been identified to
the regulator.
DOWNLOAD IN PROGRESS The CS3000 configuration download
procedure is in progress.
COAST/DB STOP OPEN The coast/DB stop input (TS 23) is open.
CUSTOMER INTERLOCK OPEN The function loss input (TS 20) is open.
MEMORY OPERATION IN
PROGRESS
Non-volatile memory is being restored.
DRIVE IS IN PROCESS OF
STOPPING
The drive is in the process of stopping.
THERE IS A DRIVE FAULT(S) The drive is faulted.
THE DRIVE IS READY. The drive is ready to run.
A STOP INPUT IS ACTIVE A keypad stop key or the selected control
source stop input is asserted.