Publication AG-UM008C-EN-P - February 2005
3-20 Configuring MicroLogix 1100/1200/1500 Controllers
To configure the processor for a master station using message-based
communication, place the processor in program mode and follow the
steps below using your programming software:
Use Worksheet 3.2 MicroLogix 1100/1200/1500 DF1 Half-Duplex
Master Station Configuration Using Message-based Communication
(page D-10) for an example configuration and to record your station’s
configuration.
1. To bring up the Channel
Configuration interface,
double-click on the Channel
Configuration icon.
2. On the Channel 1 tab, choose
DF1 Half-Duplex Master for
your Driver.
3. Choose a Message-based
Polling Mode.
4. Configure the communication
driver characteristics
according to Table 3.4.