937CU-AIHLP-DC1 Installation Instructions HART Loop Converter

Seite 2

1 Removable terminals, blue2LC display Display for showingthe measured valuesthe current output valuesthe fault messagesthe parameterization mode3

Seite 3 - Symbols Used

Number of terminal blocks max. 10Dimension drawing with screw terminalsWhen using screw terminals with test sockets the device is 124 mm (4.9 in) in

Seite 4 - Safety Notes

DIN Mounting RailThe devices are mounted on a 35 mm DIN mounting rail according to EN 60715.Example: DIN mounting rail(35 mm x 15 mm)Power RailTo redu

Seite 5 - Intended Use

Power Rail is available in two sizes:Power Rail 937A-PR08 and 937A-PR20 Three leads:• two conductors for power•one conductor for collective error mes

Seite 6 - Improper Use

MountingMounting the Isolated BarrierSnap the device onto the DIN mounting rail in a vertical downward movement. See figure below.Mounting the Termina

Seite 7 - Delivery, Transport, Disposal

ConnectionThe removable terminal blocks simplify connection and control cabinet construction significantly. These terminal blocks offer adequate space

Seite 8 - Function

+1+2+-3-45250 Ω6ERR 24 V DCPower RailHART+-mA+-Zone 0, 1, 2Div. 1, 2HARTHARTBul. 937C HART Loop Converter Installation Instructions14

Seite 9 - Assembly

Connection The following connections are available:Terminals 10 ... 12: output I (relay 1 (change-over contact))Terminals 16 ... 18: output II (rela

Seite 10

Connecting a HART Handheld to the Field DeviceYou have two options for connecting a HART handheld to the field device:Connection to terminals 22/24 o

Seite 11 - Dimensions

Polling Mode (command and answer)The isolated barrier deactivates the burst configuration of the field device. The isolated barrier performs the field

Seite 13 - Power Rail

ConfigurationConfiguring the DeviceConfigure the device using the buttons on the front side. Use the  ,, ESC, and OK buttons for navigation. The fol

Seite 14 - Mounting

Parameterization ModeAfter being switched on, the device is in display mode. If you have password protection enabled, you must enter the password ever

Seite 15 - Connection

Password ProtectionYou can activate password protection to protect parameterization from unauthorized changes. Ifpassword protection is enabled, you

Seite 16 - Div. 1, 2

Bul. 937C HART Loop Converter Installation InstructionsEntering NumbersAt the lowest menu level of the Parameter menu, you have the option of selectin

Seite 17 - Connecting t

Bul. 937C HART Loop Converter Installation Instructions Entering Floating Point FiguresAt the lowest menu level of the Parameter menu, you have the op

Seite 18 - Dynamic Query of Variables

Bul. 937C HART Loop Converter Installation InstructionsEntering a Numerical Value1. Select the parameter for which you want to enter the numerical val

Seite 19 - Time Out (communication loss)

Bul. 937C HART Loop Converter Installation InstructionsUnitAt the lowest menu level of the Unit menu, you have the option of selecting the unit type f

Seite 20 - Caution!

Bul. 937C HART Loop Converter Installation InstructionsChanging the Custom Tag of HART Variables1. Select the HART variable for which you would like t

Seite 21 - Parameterization Mode

Bul. 937C HART Loop Converter Installation InstructionsHARTcomThe HARTcom menu offers the option of specifying the method for communication between de

Seite 22 - Password Protection

Bul. 937C HART Loop Converter Installation InstructionsSelecting a ModeThe device functions as primary or secondary HART master according to

Seite 23 - Entering Numbers

1Bul. 937C HART Loop Converter Installation InstructionsSymbols UsedThis symbol warns of possible danger. Failure to heed this warning may result in p

Seite 24

Bul. 937C HART Loop Converter Installation InstructionsEditing device data: Input Defining ShortAddressThe defined short address is needed for identif

Seite 25 - Entering a Numerical Value

Bul. 937C HART Loop Converter Installation InstructionsIf the connection to the field device has been lost, the localization phase can be performed wi

Seite 26

Bul. 937C HART Loop Converter Installation InstructionsEditing device data: InputSelecting an AssignmentThe values of the selected HART variable (PV,

Seite 27

Bul. 937C HART Loop Converter Installation InstructionsEditing device data: InputDefining a CharacteristicThe choice of characteristic defines the lim

Seite 28 - The HARTcom menu offers the

Bul. 937C HART Loop Converter Installation InstructionsExampleCharacteristic 4 - 20 NE43, start value 2 bar, end value 10 barThe type of fault current

Seite 29 - Defining ComControl

Bul. 937C HART Loop Converter Installation InstructionsRelay Contact OutputsIn the Output menu, you have the option of defining relay contact outputs

Seite 30 - Selecting LocateMethod

Bul. 937C HART Loop Converter Installation InstructionsSelecting Relay Contact Output Menus1.Select the desired relay contact output using the  or 

Seite 31 - Activating Rebuild

Bul. 937C HART Loop Converter Installation InstructionsCalling up a Trip Value1.Select the Trip value menu with the  or buttons.2. If the trip value

Seite 32

Bul. 937C HART Loop Converter Installation InstructionsSelecting an AssignmentThe values of the HART variables selected here (PV, SV, TV, QV) are moni

Seite 33 - Defining the End Value

Bul. 937C HART Loop Converter Installation InstructionsYou can implement the following applications:Switching direction max, direction of operation a

Seite 34

2Bul. 937C HART Loop Converter Installation InstructionsSafety NotesThe HART Loop Converter must only be operated by trained personnel in accordance w

Seite 35 - Relay Contact Outputs

Bul. 937C HART Loop Converter Installation InstructionsDefining the Trip Point1. Enter the starting point as a floating point figure. For entering flo

Seite 36

Bul. 937C HART Loop Converter Installation InstructionsResponse delay has the following effects:When the value of the trip point is out of range (exc

Seite 37 - Trip Value

Bul. 937C HART Loop Converter Installation InstructionsCalling up a Fault Message1.Use the  or buttons to select the Fault message menu.2. If the fa

Seite 38

Bul. 937C HART Loop Converter Installation InstructionsService In the Service menu, you have the option of specifying basic device parameters.Select l

Seite 39

Bul. 937C HART Loop Converter Installation InstructionsTo protect parameterization from unauthorized changes, you can enable password protection. Info

Seite 40 - Defining the Response Delay

Bul. 937C HART Loop Converter Installation InstructionsEditing device data: Default settingsIndicators during OperationThe isolated barrier displays t

Seite 41 - Delay Delay

Bul. 937C HART Loop Converter Installation InstructionsIn normal operation, the display shows:the current values of the HART variables PV, SV, TV, QV

Seite 42 - Fault Message

Display Options for Current Output Values and HART VariablesTo select the displayed measured values or current output values, use the  and buttons.

Seite 43 - Service

Technical SpecificationsDefault SettingsThe following table provides an overview of the default settings. Information about resetting the device to th

Seite 44 - Factory Settings

Menu Parameters Default setting Custom valueOutput --- Iout3Assignment disabledCharacteristic 4 - 20 NE43Start value 0.000End value 100.0Fault current

Seite 45 - Operation

Reference to further documentationLaws, standards, or directives applicable to the intended use must be observed. In relation to hazardous areas, Dire

Seite 48 - Default Settings

Publication 937-IN003A-EN-P - April 2014 (DIR 10001099005) 814570Copyright © 2014 Rockwell Automation, Inc. All r

Seite 49

Protection of the operating personnel and the overall system is not ensured if the product is not being used according to its intended purpose.The equ

Seite 50

The respective peak values of the field device and the associated apparatus with regard to explosion protection should be considered when conne

Seite 51

The device supplies field devices and can be connected in parallel to existing HART circuits.The device analyzes up to four HART variables (PV, SV, TV

Seite 52 - (DIR 10001176476)

Operating and indicating elementsProduct Specifications AssemblyBul. 937C HART Loop Converter Installation Instructions711 234 5629ERR PWR1 2OUT3 48ES