Rockwell Automation Publication 6000-IN007A-EN-P - October 2014 41
Commissioning Chapter 3
Verify Operation of Frequency Steps
There are two parts to this procedure, increasing the frequency in set increments
and increasing the frequency to a specific rated frequency.
Increase Frequency by Step
1. From the Main Interface Screen, press the Set Frequency: input field.
2. In the Set Freq: dialog box, enter a value of “10” and press .
Press to confirm.
TIP
Durh
During the Control System Check procedure, an “Abnormal Output Voltage
Warning” will appear, as the procedure is done without MV and the Control
System is expecting an output voltage. Ignore this warning for this procedure.
TIP
The Set Frequency and Actual Frequency occasionally will not show the exact
integral value selected, due to internal data conversion in the HMI program.