Read register 4 to determine whether bits 8 and 10 are set,
signifying that the common clock is being driven by
another module in the rack. If they are not set, then set
registers 5 and 6 on this module to the value 64. This will
enable common clock on this module. Bits 8 and 10 on
register 4 should now be set.
Monitor registers 0 and 1. Verify that they contain numbers
proportional to the analog value on their respective
channels. This confirms that the installation is complete.
Refer to table 1 for the approximate voltages or currents
that should be read.
Table 1
 +
 +  
ă4095 +1.0V +10.0V 20 ma
ăă819 +ă.2V +2.0V ă4 ma
ăăă0 0.0V 0.0V ă0 ma
-4095 -1.0V -10.0V ă -
Step 9. Determine offset and gain compensation. This is
necessary because manufacturing tolerances on the
module can result in small offset and gain differences (See
figure 3.3).
VOLTS0
4095
10
COUNTS
CORRECTED_VALUE%
OFFSET
RAW_DATA%
Figure 3.3 Ć Offset and Gain