18Ć24
for each port on the PMI Processors associated with the
selected UDC module (A and B).
Step 3. Enter U" to select the UDC analog outputs, A" to select
the PMIĆA analog outputs, or B" to select the PMIĆB
analog outputs.
Step 4. Enter the port (1Ć4) you want to configure.
Step 5. If you entered U" (UDC) above, enter the task name (for
LOCAL variable), the variable name or register and bit
number of the variable you want to assign to the selected
UDC meter port.
If you selected 
A
" (PMIĆA) or B" (PMIĆB), select the
parameter you want to assign to the port. Use the Up
Arrow and Down Arrow keys to scroll through the list of
available parameters displayed on the screen.
Step 6. Enter a minimum and maximum value for the selected
variable in the V
al @ -10V
" and V
al @ +10V
" fields,
respectively.
Step 7. When you are finished setting up the UDC and PMI meter
ports, press <ESC> to return to the Monitor menu.