5–3PanelView Terminal Setup
Publication 2711-6.2
To set up the block transfers for Remote I/O Communications:
1. Click the Block Transfer button.
The Block Transfer dialog opens.
Block Transfer 1 assignment
Block Transfer 2 assignment
Check Pass Through box
Select 0
2. Enter data for the 2 block transfers shown above.
For Block Transfer 1:
Check the Enabled box
Type N7:0 in the Address field
Select W (for Write) from the Mode box.
Select 10 from the Length box.
For Block Transfer 2:
Check the Enabled box
Type N7:10 in the Address field
Select R (for Read) from the Mode box.
Select 10 from the Length box.
3. Check the Pass Through box.
4. Select 0 from the Block Transfer Timeout box.
5. Click OK to return to the Communication Setup dialog.
6. Click OK to return to the Terminal Setup dialog.
Skip ahead to page 5–6 to set Terminal Power-Up Options.