Rockwell Automation Publication 750COM-UM001E-EN-P - October 2013 27
Configuring the Adapter Chapter 3
1. Verif y that Parameter 36 - [BOOTP] is set to ‘1’ (Enabled).
2. Note the adapter’s hardware Ethernet Address (MAC), which will be used
in step 7.
There are two ways to do this:
Remove the PowerFlex 755 drive cover and locate the adapter’s
hardware Ethernet Address (MAC) label on the drive’s Main Control
Board (Figure 4
).
Figure 4 - Adapter Hardware Address Label Location
Use the HIM to scroll to drive Port 13 and access the embedded
EtherNet/IP adapter DIAGNOSTIC folder screen. Then scroll to
Diagnostic Items 43…48 (HW Addr 1…6) to view the adapter’s
hardware Ethernet Address (MAC). Finally, convert these decimal
values to a hex value.