Rockwell-automation 20D DriveLogix Controller for PowerFlex 700S Phase Bedienungsanleitung

Stöbern Sie online oder laden Sie Bedienungsanleitung nach Ausrüstung Rockwell-automation 20D DriveLogix Controller for PowerFlex 700S Phase herunter. Rockwell Automation 20D DriveLogix Controller for PowerFlex 700S Phase I Drives User Manual Benutzerhandbuch

  • Herunterladen
  • Zu meinen Handbüchern hinzufügen
  • Drucken
  • Seite
    / 18
  • Inhaltsverzeichnis
  • LESEZEICHEN
  • Bewertet. / 5. Basierend auf Kundenbewertungen
Seitenansicht 0
Installation Instructions
DriveLogix Controller for PowerFlex 700S
Phase I Drives
What This Kit Contains
Verify that your kit contains the items listed in the following table. If your
kit does not contain the correct items, contact your Allen-Bradley sales
representative.
Tools That You Need
Phillips® screwdriver
Nut driver or wrench
Flathead screwdriver
Phillips® is a registered trademark of Phillips Screw Company
!
ATTENTION: To avoid an electric shock hazard, verify that the
voltage on the bus capacitors has discharged before performing
any work on the drive. Measure the DC bus voltage at the +DC &
–DC terminals of the Power Terminal Block. The voltage must
be zero.
!
ATTENTION: HOT surfaces can cause severe burns. Do not
touch the heatsink surface during operation of the drive. After
disconnecting power allow time for cooling.
!
ATTENTION: This drive contains ESD (Electrostatic
Discharge) sensitive parts and assemblies. Static control
precautions are required when installing, testing, servicing or
repairing this assembly. Component damage may result if ESD
control procedures are not followed. If you are not familiar with
static control procedures, reference A-B publication 8000-4.5.2,
“Guarding Against Electrostatic Damage” or any other
applicable ESD protection handbook.
!
ATTENTION: This product contains a 3V Lithium battery.
Perchlorate Material - special handling may apply.
See www.dtsc.ca.gov/hazardouswaste/perchlorate
Quantity Description
1 DriveLogix Controller assembly (including bracket and battery)
2 50 - pin “stacker” connector
1 Disposable Static Discharge Wrist-strap
Seitenansicht 0
1 2 3 4 5 6 ... 17 18

Inhaltsverzeichnis

Seite 1 - Phase I Drives

Installation InstructionsDriveLogix Controller for PowerFlex 700S Phase I DrivesWhat This Kit ContainsVerify that your kit contains the items listed

Seite 2 - Additional Information

10 DriveLogix Controller for PowerFlex 700S Phase I Drives Step 8: Installing the New DriveLogix Controller AssemblyTask DescriptionAlign the slotted

Seite 3 - Step 1: Removing Power

DriveLogix Controller for PowerFlex 700S Phase I Drives 11 Step 9: Completing the Installation of the DriveLogix Controller AssemblyTask DescriptionTi

Seite 4 - Covers from the Control

12 DriveLogix Controller for PowerFlex 700S Phase I Drives Step 10: Connecting the DriveLogix Controller to a DeviceConnecting to Flex I/O1. Connect t

Seite 5 - Controller Assembly

DriveLogix Controller for PowerFlex 700S Phase I Drives 13 2. Connect the other end of the cable to the first (right-most) Flex I/O module on the stri

Seite 6 - Communication Daughter

14 DriveLogix Controller for PowerFlex 700S Phase I Drives 1. Select the appropriate cable.• The 1756-CP3 cable attaches to the DriveLogix Controller

Seite 7 - Step 5: Installing the

DriveLogix Controller for PowerFlex 700S Phase I Drives 15 2. Connect the cable to the serial port on the DriveLogix Controller. Step 11: Installing t

Seite 8 - Step 6: Connecting the

16 DriveLogix Controller for PowerFlex 700S Phase I Drives Monitoring the DriveLogix Controller LEDs!ATTENTION: The controller LEDs are only operatio

Seite 9 - Stacker Connectors

DriveLogix Controller for PowerFlex 700S Phase I Drives 17 DriveLogix Controller LEDs RUN Green Off • No task(s) running.• Controller in Program mode

Seite 10 - Assembly

www.rockwellautomation.comAmericas: Rockwell Automation, 1201 South Second Street, Milwaukee, WI 53204 USA, Tel: (1) 414.382.2000, Fax: (1) 414.382.4

Seite 11 - Installation of the

2 DriveLogix Controller for PowerFlex 700S Phase I Drives What You Need To DoTo remove an existing DriveLogix controller from the drive:❑ Step 1: Remo

Seite 12 - Connecting to Flex I/O

DriveLogix Controller for PowerFlex 700S Phase I Drives 3 Step 1: Removing Power from the Drive1. Turn off and lock out input power. Wait five minutes

Seite 13 - Serial Port

4 DriveLogix Controller for PowerFlex 700S Phase I Drives Step 2: Removing the Covers from the Control AssemblyTask DescriptionLoosen the captive scre

Seite 14

DriveLogix Controller for PowerFlex 700S Phase I Drives 5 Step 3: Removing the Existing DriveLogix Controller AssemblyIf there is no Communication Dau

Seite 15

6 DriveLogix Controller for PowerFlex 700S Phase I Drives Step 4: Removing the Communication Daughter CardTask DescriptionLoosen the two screws that s

Seite 16 - Monitoring the DriveLogix

DriveLogix Controller for PowerFlex 700S Phase I Drives 7 Step 5: Installing the Communication Daughter CardTask DescriptionAlign the Communication Da

Seite 17

8 DriveLogix Controller for PowerFlex 700S Phase I Drives Step 6: Connecting the BatteryTask DescriptionInsert the battery connector into the socket o

Seite 18 - Specifications

DriveLogix Controller for PowerFlex 700S Phase I Drives 9 Step 7: Installing the Stacker ConnectorsTask DescriptionIdentify the ends of the stacker co

Kommentare zu diesen Handbüchern

Keine Kommentare