72 Rockwell Automation Publication 20COMM-UM015B-EN-P - July 2013
Chapter 4 Configuring the I/O
Figure 14 - MicroLogix 1100/1400 Message Configuration Screens for the Control
Timeout
General Tab Box Setting
This Controller (data for MicroLogix 1100)
Channel 1 (integral). Controller port to which the network is connected.
Communication Command 500CPU Write. The controller type and command type for the controller to read or write data.
Because the MicroLogix 1100 is part of the SLC-500 controller family, the ‘500CPU’ controller type
was selected. The ‘Write’ command type was selected to write the control timeout value to the drive.
Data Table Address
(1)
N20:0. An unused controller data table address containing the control timeout value to be written.
Size in Elements
(2)
1. Number of elements (words) to be transferred. Each element size is a 16-bit integer.
Target Device (data for adapter/drive)
Message Timeout 5. Message timeout duration in seconds.
Data Table Address
(3)
N42:3. Specific starting address of the destination file in the drive.
Routing Information File RI9:0. An unused routing information file for the controller.
MultiHop Tab Box Setting
To Address 10.91.100.79. The IP address of the adapter connected to the drive.
(1) For details on data table addresses for this example project, see Table 11Table 14 starting on page 98.
(2) For details to determine element size for a specific drive, see Understanding Controller Data Table Addresses
on page 97.
(3) For details on setting the control timeout value and its function, see N-Files
on page 192. The Control Timeout (N42:3) is stored in RAM. If the 20-
COMM-ER adapter is power cycled, the Control Timeout Message must be re-sent. If the Control Timeout is not changed from a non-zero value, the
control message (page 75
) will error out.
TIP
The Control Timeout (N42:3) must be changed to a non-zero value (5…20 seconds
recommended). If the Control Timeout is not changed from a non-zero value, the
control message (page 75
) will error out. The Control Timeout is stored in RAM. If
the adapter is power cycled, the Control Timeout Message must be re-sent.