FLEX I/O Isolated Output HART Analog Module 19
Publication
1794-IN120C-EN-P - April 2009
Cyclic HART Input Data
The HART input data holds the primary variables for the "live" HART
device, and other information gathered during the normal HART
scan. Additional "documentary" data is available through the pass
through message interface in the device information tables. Pass
through messages are defined in detail in the User Manual.
Format Values
Format Format name 0.0 mA 2.0 mA 4.0 mA 20.0 mA 22.0 mA
0 0…20 mA in
Milliamps
0 2000 4000 20000 22000
1 0…20 mA in % Full
Scale
0 1000 2000 10000 11000
3 0…20 mA in UINT 0 6554 13107 65535
65535
(1)
4 4…20 mA in
Milliamps
2000
(1)
2000 4000 20000 22000
7 4…20 mA in UINT
0
(1)
0
(1)
0 65535
65535
(1)
14 4…20 mA in % Full
Scale
-1250
(1)
-1250 0 10000 11250
(1)
These values are under, or over the supported user range, and are clamped at the lowest/highest
supported values.
IMPORTANT
The HART Input Data for a channel may be zeroes if HART communications
is disabled for that channel. For more information on disabling HART
communications, refer to the Disable HART communications and HART
CMD 3 Disable functions in the Configuration Map table.