Publication 1794-IN083B-EN-P - November 2004
Installation Instructions
FLEX I/O Digital Input/Output Modules
Cat. No. 1794-IB10XOB6, 1794-IB16XOB16P
European Hazardous Location Approval
The following module is European Zone 2 approved: 1794-IB10XOB6.
Important User Information
Solid state equipment has operational characteristics differing from those of
electromechanical equipment. Safety Guidelines for the Application, Installation and
Maintenance of Solid State Controls (Publication SGI-1.1 available from your local Rockwell
Automation sales office or online at http://www.ab.com/manuals/gi) describes some
important differences between solid state equipment and hard-wired electromechanical
devices. Because of this difference, and also because of the wide variety of uses for solid
state equipment, all persons responsible for applying this equipment must satisfy themselves
that each intended application of this equipment is acceptable.
In no event will Rockwell Automation, Inc. be responsible or liable for indirect or
consequential damages resulting from the use or application of this equipment.
The examples and diagrams in this manual are included solely for illustrative purposes.
Because of the many variables and requirements associated with any particular installation,
Rockwell Automation, Inc. cannot assume responsibility or liability for actual use based on
the examples and diagrams.
No patent liability is assumed by Rockwell Automation, Inc. with respect to use of
information, circuits, equipment, or software described in this manual.
Reproduction of the contents of this manual, in whole or in part, without written permission
of Rockwell Automation, Inc. is prohibited.
Throughout this manual we use notes to make you aware of safety considerations.
WARNING
Identifies information about practices or circumstances that can cause
an explosion in a hazardous environment, which may lead to personal
injury or death, property damage, or economic loss.
IMPORTANT
Identifies information that is critical for successful application and
understanding of the product.
ATTENTION
Identifies information about practices or circumstances that can lead to
personal injury or death, property damage, or economic loss. Attentions
help you:
identify a hazard
avoid a hazard
recognize the consequence
ATTENTION
Environment and Enclosure
This equipment is intended for use in a Pollution Degree 2
industrial environment, in overvoltage Category II applications
(as defined in IEC publication 60664-1), at altitudes up to 2000
meters without derating.
This equipment is considered Group 1, Class A industrial
equipment according to IEC/CISPR Publication 11. Without
appropriate precautions, there may be potential difficulties
ensuring electromagnetic compatibility in other environments
due to conducted as well as radiated disturbance.
This equipment is supplied as "open type" equipment. It must
be mounted within an enclosure that is suitably designed for
those specific environmental conditions that will be present and
appropriately designed to prevent personal injury resulting
from accessibility to live parts. The interior of the enclosure
must be accessible only by the use of a tool. Subsequent
sections of this publication may contain additional information
regarding specific enclosure type ratings that are required to
comply with certain product safety certifications.
See NEMA Standards publication 250 and IEC publication
60529, as applicable, for explanations of the degrees of
protection provided by different types of enclosure. Also, see
the appropriate sections in this publication, as well as the
Allen-Bradley publication 1770-4.1 ("Industrial Automation
Wiring and Grounding Guidelines"), for additional installation
requirements pertaining to this equipment.
WARNING
When you insert or remove the module while backplane
power is on, an electrical arc can occur. This could cause an
explosion in hazardous location installations. Be sure that
power is removed or the area is nonhazardous before
proceeding.
ATTENTION
FLEX I/O is grounded through the DIN rail to chassis
ground. Use zinc plated yellow-chromate steel DIN rail to
assure proper grounding. The use of other DIN rail
materials (e.g. aluminum, plastic, etc.) that can corrode,
oxidize, or are poor conductors, can result in improper or
intermittent grounding.
WARNING
If you connect or disconnect wiring while the field side
power is on, an electrical arc can occur. This could cause an
explosion in hazardous location installations. Be sure that
power is removed or the area is nonhazardous before
proceeding.
ATTENTION
Preventing Electrostatic Discharge
This equipment is sensitive to electrostatic discharge, which
can cause internal damage and affect normal operation.
Follow these guidelines when you handle this equipment:
Touch a grounded object to discharge potential static.
Wear an approved grounding wriststrap.
Do not touch connectors or pins on component
boards.
Do not touch circuit components inside the
equipment.
If available, use a static-safe workstation.
European Zone 2 Certification (The following applies when the
product bears the EEx Marking)
This equipment is intended for use in potentially explosive atmospheres as
defined by European Union Directive 94/9/EC.
The LCIE (Laboratoire Central des Industries Electriques) certifies that this
equipment has been found to comply with the Essential Health and Safety
Requirements relating to the design and construction of Category 3
equipment intended for use in potentially explosive atmospheres, given in
Annex II to this Directive. The examination and test results are recorded in
confidential report No. 28 682 010.
Compliance with the Essential Health and Safety Requirements has been
assured by compliance with EN 50021.
IMPORTANT
Observe the following additional Zone 2 certification
requirements.
This equipment is not resistant to sunlight or other
sources of UV radiation.
The secondary of a current transformer shall not be
open-circuited when applied in Class I, Zone 2
environments.
Equipment of lesser Enclosure Type Rating must be
installed in an enclosure providing at least IP54
protection when applied in Class I, Zone 2
environments.
This equipment shall be used within its specified
ratings defined by Allen-Bradley.
Provision shall be made to prevent the rated voltage
from being exceeded by transient disturbances of
more than 40% when applied in Class I, Zone 2
environments
Seitenansicht 0
1 2 3 4 5 6

Inhaltsverzeichnis

Seite 1 - Installation Instructions

Publication 1794-IN083B-EN-P - November 2004Installation InstructionsFLEX I/O Digital Input/Output ModulesCat. No. 1794-IB10XOB6, 1794-IB16XOB16PEurop

Seite 2 - AVERTISSEMENT

2 Publication 1794-IN083B-EN-P - November 2004North American Hazardous Location ApprovalThe following modules are North American Hazardo

Seite 3 - (1794-TB3 show

3Publication 1794-IN083B-EN-P - November 20041794-TB3 and -TB3S Terminal Base Wiring for the 1794-IB10XOB62 and 3-Wire Input Wiring for 1

Seite 4 - Specifications

4 Publication 1794-IN083B-EN-P - November 2004Configuring Your ModuleYou configure your module by setting bits in the configuration word

Seite 5 - 5

5Publication 1794-IN083B-EN-P - November 2004Derating Chart for the 1794-IB16XOB16PGeneral SpecificationsModule Location 1794-IB10XOB6 -

Seite 6

Publication 1794-IN083B-EN-P - November 2004 6 PN 957782-96Supersedes Publication 1794-IN083A-EN-P - December 2002, 1794-IN024C-EN-P - November 2002 C

Kommentare zu diesen Handbüchern

Keine Kommentare