4 FLEX Integra 16 Protected Sink Output Module
Publication 1793-5.11 - December 1999
Wiring
This module is available with 2 styles of connectors; screw-cage
(1793-OV16P) and spring-clamp (1793-OV16PS). Refer to the wiring
figure below.
1. Connect individual output wiring to terminals 0 through 15 on row A.
2. Connect associated power terminal to terminals on row B.
3. Connect +24V dc voltage to terminal V on row B.
4. Connect 24V dc common to terminal COM on row A.
5. If daisy-chaining +24V dc from this module to the next FLEX Integra
module, connect a jumper from terminal V to terminal 8 on the next 8
point Integra module or terminal V on the next 16 point Integra
module.
6. If daisy-chaining 24V dc common from this module to the next FLEX
Integra module, connect a jumper from terminal COM on this module
to terminal 0 on the next 8 point Integra module or to terminal COM
on the next 16 point Integra module.
.
!
ATTENTION: Total current draw through the module’s
(V) voltage terminals is limited to 10A. Separate power
connections to the module may be required.
1793-OV16P
1793-OV16PS
0 123456789101112131415
A
B
41814
VV
COM
COM
A
B
01 2345678 9101112131415COM
COM
VV
41816
Where: COM = common, V = + 24V dc, 0 thru 15 = outputs