8 ArmorBlock MaXum 8 Output Module Series B
Publication 1792D-IN003B-EN-P - September 2000
Communicate with Your ArmorBlock MaXum
I/O Module
This ArmorBlock module’s I/O is exchanged with the master through
a poll, change-of-state, or cyclic connection.
The module consumes and produces output data as follows:
Cyclic - allows configuration of the block as an I/O client. The block
will produce and consume its I/O cyclically at the rate configured.
Polled - a master initiates communication by sending its polled I/O
message to the module. This 8 output module consumes the
message, updates outputs and produces a response. The response
has output faults and the status of the Auxiliary power.
Change-of-state - productions occur when an input changes or a
fault condition occurs. If no input or fault condition change occurs
within the expected packet rate, a heartbeat production occurs. This
heartbeat production tells the scanner module that the I/O module is
alive and ready to communicate.
Refer to the table below for the word/bit definitions.
Type of I/O Connections Consumes Produces
Cyclic 1 Bytes 2 Bytes
Polled 1 Bytes 2 Bytes
Change-of-State 1 Bytes 2 Bytes
Bit 0706050403020100
Produces 0 OFLT7 OFLT6 OFLT5 OFLT4 OFLT3 OFLT2 OFLT1 OFLT0
Produces 1 RSVP OPWR RSVP RSVP RSVP RSVP RSVP RSVP
Consumes 0 O7 O6 O5 O4 O3 O2 O1 O0
Where: OFLT = Output Fault OPWR = Output Power O = Output RSVP = Reserved