10 ArmorBlock MaXum 16 Input Module with Complete Diagnostics
Publication 1792D-IN053A-EN-P - August 2002
•1792D-IN009 ArmorBlock MaXum Cable Base Installation Guide
•DN-6.7.2 DeviceNet Cable Planning and Installation Manual
Communicate With Your ArmorBlock MaXum Module
This ArmorBlock module’s I/O is exchanged with the master through
a polled, change-of-state, or cyclic connection.
The module consumes and produces input data as follows:
Cyclic - allows configuration of the block as an I/O client. The block
will produce its I/O cyclically at the rate configured.
Polled - a master initiates communication by sending its polled I/O
message to the module. The 16 input module scans the inputs and
fault bits producing a response that reflects their status.
Change of State - productions occur when an input changes or a
fault condition occurs. If no input or fault condition change occurs
within the expected packet rate, a heartbeat production occurs. This
heartbeat production tells the scanner module that the module is alive
and ready to communicate.
Refer to the table below for the word/bit definitions.
Note: If you are using DeviceLogix, please refer to publication no.
1792-TD001 for the alternate I/O assemblies for DeviceLogix.
Type of I/O Connections Consumes Produces
Cyclic 0 Byte 6 Bytes
Polled 0 Byte 6 Bytes
Change-of-State 0 Byte 6 Bytes
Bit 0706050403020100
Produced 0 In 7In 6In 5In 4In 3In 2In 1In 0
Produced 1 In 15 In 14 In 13 In 12 In 11 In 10 In 9 In 8
Produced 2 ISC-7 ISC-6 ISC-5 ISC-4 ISC-3 ISC-2 ISC-1 ISC-0
Produced 3 ISC-15 ISC-14 ISC-13 ISC-12 ISC-11 ISC-10 ISC-9 ISC-8
Produced 4 OW-7 OW-6 OW-5 OW-4 OW-3 OW-2 OW-1 OW-0
Produced 5 OW-15 OW-14 OW-13 OW-12 OW-11 OW-10 OW-9 OW-8
Where: I = Input ISC = Input Short Circuit in Sensor Source Voltage OW = Off Wire