Rockwell-automation 1790D-XXXX DeviceNet Digital Base Terminal Block C Bedienungsanleitung Seite 26

  • Herunterladen
  • Zu meinen Handbüchern hinzufügen
  • Drucken
  • Seite
    / 28
  • Inhaltsverzeichnis
  • LESEZEICHEN
  • Bewertet. / 5. Basierend auf Kundenbewertungen
Seitenansicht 25
26 DeviceNet Digital Base Terminal Block CompactBlock LDX I/O
Publication
1790-IN012B-EN-P - July 2008
ESD immunity IEC 61000-4-2:
8 kV air discharges
Radiated RF
immunity
IEC 61000-4-3:
10V/m with 1 kHz sine-wave 80%AM from 80…1000 MHz
10V/m with 1 kHz sine-wave 80%AM from 1.4…2 GHz
10V/m with 200 Hz 50% Pulse 100%AM at 900 MHz
EFT/B immunity IEC 61000-4-4:
±2 kV at 5 kHz on signal ports
±2 kV at 5 kHz on communications ports
Surge transient
immunity
IEC 61000-4-5:
±1 kV line-line(DM) and ±2 kV line-earth(CM) on signal ports
±2 kV line-earth(CM) on communications ports
Conducted RF
immunity
IEC 61000-4-6:
10V rms with 1 kHz sine-wave 80%AM from 150 kHz…80 MHz
Environmental