12 ControlNet NetChecker
Rockwell Automation Publication 1788-UM001B-EN-P - August 2012
Connect to the Network
Connect the NetChecker to the network in one of these ways:
Use the provided cable and BNC T, as shown in the left example. This method requires
you to break the trunk to install the BNC T, which disrupts a running system. The
BNC T is intended for temporary use only. We do not recommend leaving the BNC T
installed.
Use the provided BNC T with a 1786-TCAP tap and 1786-BNCP barrel connector, as
shown in the right example. The tap, 1786-TCAP, and 1786-BNCP connector must be
purchased separately. The tap can be left in the system for testing purposes, but the tap
must not be left unconnected. Install a 1786-TCAP on all unused taps.
If you do not want to open the network, you can install some free taps for testing. With a
redundant network, you can temporarily disconnect one of a node’s taps from the network and
test from this. Recognize, however, that you are removing a node from the network. Test that
node later from a different location on the network.
INPUT
Node On Line
Push ON
Control Net™ Net Checker
TRAFFIC
LM
7
6
5
4
3
2
1Min
Max
H
Low Battery
BargraphDiagnostic
Signal (x1/4)
GND
Trigger
OFF
ON
Push ON
Output to Scope
Power Supply
Node Finder
Threshold
Buzzer
Stow Edges
Illegal Framing
Pass/Fail
Ext
Power
5VDC
0,25A
Poor Signal
Quality
(
(
(
(
(
(
(
(
3231-M
Provided Cable
Provided BNC T
ControlNet Trunk
Tap Drop
NetChecker
NetChecker
1786-TCAP
ControlNet Trunk
Tap
1786-BNCP
Provided BNC T
Seitenansicht 11