Troubleshoot the Ethernet Status Indicators
STAT
100M
10M
ENET Status
ENET Transmit
Indicator Color Description Probable Cause Recommended
Action
STAT Solid red Critical hardware fault Controller requires
internal repair
Contact your local
Allen-Bradley
distributor
Blinking red Hardware or software fault
(detected and reported via
a code)
Fault-code
dependent
Contact Technical
Support at
440.646.3223 to
diagnose the
problem.
Off Module is functioning
properly but it is not
attached to an active
Ethernet network
Normal operation Attach the controller
and interface module
to an active Ethernet
network
Solid Green Ethernet channel 2 is
functioning properly and
has detected that it is
connected to an active
Ethernet network
Normal operation No action required
100 M or
10 M
Green Lights (green) briefly when
the Ethernet port is
transmitting a packet. It
does not indicate whether
or not the Ethernet port is
receiving a packet.